Service difficulty report · Valve · Boeing 737990ER

Difficulty date
June 5, 2015
Submitted
June 5, 2015
Operation
Air carrier
Aircraft
N433AS
Make and model
Boeing 737990ER
Aircraft serial
41704
Aircraft time
6,358 hours, 2,059 cycles
Part
Valve
Part number
3989084
Part serial
20258
Condition
Failed
Location
A/C Bay
Part time
6,354 hours, 2,055 cycles
Stage of operation
IN
How discovered
O
Nature of condition
O
Precautionary procedure
K

As reported to the FAA. Reports are unverified, and codes are left as the FAA publishes them.

What was found

ENGINEERING REQUEST PAX REPORT OF HOT TEMPS IN THE FWD CABIN. ACCOMPLISH BITE TEST OF NR 1 & NR 2 PACK ZONE TEMP CONTROLLERS AND REPLACE TEMP SENSOR FILTERS. ACFT GROUNDED. ACCOMPLISHED BITE TEST, NUMEROUS TIMES, BOTH PACK/ZONE TEMPERATURE CONTROLLERS REF AMM 21-61-00-700-806-002 IAW TSR STEP 1. NO 1 TEMP CONTROLLER SHOWS NO FAULTS. NO 2, TEMP CONTROLLER SHOWS 2 FAULTS (1) ZONE FAULTS RT FWD CAB TRIM, AND 2 THIS PACK TCV FAULT LIGHT. FOUND DISCONNECTED AIR DUCT/SLEEVE IN E/E LT REF IPC 21-22-07-01, ITEM 60. SECURED SLEEVE/DUCT & REPLACED BOTH FWD & AFT ZONE PAX CABIN TEMP SENSOR FILTERS IAW TSR STEP 2. FOUND THEM SLIGHTLY DIRTY. ABLE TO RESET ZONE FAULT ON NR 2 TEMP CONTROLLER, BUT UNABLE, HARD FAIL,TO RESET THE TCV 2 FAULT LIGHT. REPLACED TCV 2, V141, REF AMM 21-51-10-400-801, OPS CK NORMAL. PULLED & RESET 3 TOTAL C/BS. ACCOMPLISHED STEP 3 TSR, VERIFIED GOOD AIR FLOW FROM ROW 6 THU 17 REF AMM 21-00-00-800-803.