Service difficulty report · Sensor · Boeing 737990ER

Difficulty date
July 26, 2021
Submitted
July 28, 2021
Operation
Air carrier
Aircraft
N477AS
Make and model
Boeing 737990ER
Aircraft serial
40716
Aircraft time
21,864 hours, 6,851 cycles
Part
Sensor
Condition
Dirty
Location
Cockpit Temp
Stage of operation
NR
How discovered
O
Nature of condition
N
Precautionary procedure
O

As reported to the FAA. Reports are unverified, and codes are left as the FAA publishes them.

What was found

CONT CABIN 'ZONE TEMP' ILLUMINATES ON RECALL AND EXTINGUISHES WITH MASTER CAUTION RESET. GROUNDED - YES. PACK/ZONE TEMP CONTROLLER BITE PER B737-900 FIM 21-62 TASK 801 SHOWED FAULT FOR CONTROL CABIN TEMP CONTROL VALVE BUT VERIFY TEST DID NOT CONFIRM FAULT. FOUND CONTROL CABIN TEMP SENSOR AND FILTER DIRTY - CLEANED SENSOR AND REPLACED FILTER. PERFORMED CABIN TEMP CONTROL AND INDICATION OPERATIONAL TEST PER B737-900 AMM 21-61-00-700-807-002 AND PZTC BITE PER ABOVE FIM - ALL TESTS PASS.