Service difficulty report · Sensor · Boeing 767300

Difficulty date
May 16, 2007
Submitted
May 19, 2007
Operation
Air carrier
Aircraft
N585HA
Make and model
Boeing 767300
Aircraft serial
24257
Aircraft time
81,028 hours, 15,504 cycles
Part
Sensor
Condition
Unknown
Location
Pack Temp
Stage of operation
IN
How discovered
O
Nature of condition
J
Precautionary procedure
K

As reported to the FAA. Reports are unverified, and codes are left as the FAA publishes them.

What was found

ETOPS SIGNIFICANT SYSTEM, CABIN TEMPS ON THE GRN PRIOR TO DEPARTURE VERY HOT BOTH PACKS ON ALL TROM VALVES CLOSED PACK OUT L NO READING, R- -2, DUCT PRESS L 32, R 32, PACK FLOW L 0,R 0, RAM AIR DOOR L 0.0, R 0.02, CABIN TEMPS F80, M82, A82. PERFORMED BITE OF ZONE TEMP CONTROLLER PER FIM 21-60-00 AND BITE OF BOTH PACK CONTROLLERS PER FIM 21-51-00 NO FAULTS NOTED HEATED A/C TO 80 THEN COOLED TO 68 IN 10 MIN REMOVED AND REPLACED L PACK TEMP SENSOR PER AMM 21-51-08, OPS CK GOOD.