Service difficulty report · Wire Harness · Beech C90A

Difficulty date
February 6, 2008
Submitted
March 11, 2008
Operation
General aviation
Aircraft
N4764A
Make and model
Beech C90A
Aircraft serial
LJ1161
Part
Wire Harness
Condition
Misinstalled
Location
A/C Start Cont
Stage of operation
IN
How discovered
V
Nature of condition
W
Precautionary procedure
K

As reported to the FAA. Reports are unverified, and codes are left as the FAA publishes them.

What was found

AIR CONDITIONER NOT COOLING. FOUND WIRING FOR AC START CONTROL PANEL AS WELL AS COMPRESSOR CLUTCH NOT IN PROPER CONFIGURATION IAW WIRING PRINT. AFTER PROPER INSTALLATION OF WIRING AND SUBSEQUENT OPS CHECK, THE MOTOR AND SYS, THE AIR CONDITIONER WOULD CYCLE IN AND OUT OF ITS SOFT START CYCLE. THIS IN TURN CREATED EXCESSIVE HEAT IN THE LOAD RESISTOR CIRCUIT. THIS CYCLING CONTINUED UNTIL AT SOME POINT THE SOFT START CIRCUIT FAILED, WHICH CAUSED THE LOAD RESISTOR TO OVERHEAT AND MELT THE PHENOLIC BLOCK SHIELDS WHICH CAUGHT FIRE AND DAMAGED THE IMMEDIATE SURROUNDING STRUCTURE OF THE NOSE COMPARTMENT. PROBABLE CAUSE WOULD INDICATE FAILURE OF THE AC START CONTROL PANEL CIRCUITRY THAT SUBSEQUENTLY LEAD TO A NOSE COMPARTMENT FIRE. RECOMMENDATION: ROUTINE INSPECTION AND OPERATION CHECK OF THE AC SYS, TO INCLUDE THE START CONTROL PANEL SOFT START SYS. (K)