KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR(CFD)–

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 12 of 30 If a curved heat protection shield is not available place a flat heat protection shield (i.e.

aluminum plate) behind the sensing element being heated and hold the heat gun 1.00 to

1.25 inch (2.54 to 3.18 cm) from the sensing element as shown in Figure 3.

Figure 3: Heat gun using heat protection shield side view B. RC - Preparation

(1) Heat Gun Temperature Verification at sensing element position:

NOTE: To ensure that the Heat Gun Temperature is consistent during all testing, this verification procedure must be performed prior to testing the first sensing element of each alarm set point and repeated after every four hours of testing or when the sensing element set point changes or when the ambient conditions in the test location change but not less than once per shift.

(a) Install the heat protection shield on the heat gun as shown in Figure 1.

(b) Connect the thermocouple to the Digital Mu ltimeter (DMM) or Digital Temperature Meter (DTM) and set the DMM or DTM to measure temperature.

(c) Turn on the heat gun and set airflow rate to maximum on the heat gun if the setting is available.

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR (CFD) –

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION

January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 13 of 30

(d) Place the thermocouple at the center of the heat protection shield, not touching the shield, at the approximate location the sensing element will be placed as shown in Figure 1 and Figure 2.

(e) Set the heat gun temperature so that the thermocouple reads the Thermocouple Test Temperature value specified in Table 1 for the correct Salt Type Letter.

NOTE: It is recommended that the Heat Gun setting temperature be initially set high enough such to achieve a Thermocouple Test Temperature that uses approximately ½ the allowable temperature tolerance defined in Table 1.

NOTE: For Heat Guns with a digital display, the Heat Gun display temperature will typically be higher than the temperature at the thermocouple.

NOTE: During Heat Gun Temperature Settings calibration to achieve the Thermocouple Test Temperature, the thermocouple temperature will slightly vary up and down according to the thermal regulation of the Heat Gun. The temperature values recorded should be the average of the observed results.

(f) Verify and record that the center thermocouple temperature value is within the Thermocouple Test Temperature value tolerance specified in Table 1.

(g) Move and place the thermocouple approximately 0.33 inch (0.85 cm) from the centerline of the heat protection shield left or right at the approximate location the sensing element will be placed as shown in Figure 1 and Figure 2.

NOTE: If measuring the 2 nd location right of centerline, route thermocouple from the right. If measuring the 2 nd location left of centerline, route thermocouple from the left.

NOTE: The Heat Gun 2 nd or off-axis location may be below the lower limit in the Table 1 as the temperature may reduce near the edges left or right of center test position.

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR (CFD) –

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION

January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 14 of 30

(h) Record the second or off-axis thermocouple value.

(i) Calculate the two (2) point average temperature of the center point and second or offaxis thermocouple readings.

EXAMPLE Salt Type Letter Step 6 Center Thermocouple Temperature (T center) Step 2nd Thermocouple Temperature (T 2 nd ) 2 pt Average Thermocouple Test Temperature A 290 °F / 143 °C 260 °F / 127 °C 275 °F / 135 °C

FORMULA: 2pt Average Thermocouple Test Temperature = (T center + T 2 nd)/2 = (290 °F + 260 °F)/2 = 275 °F

(j) If the above 2 Point (pt) average Thermocouple Test Temperature value is not within the tolerance allowed in Table 1 using a Center and Left off axis position or Center and Right off axis position, attempt steps 4) through 9) trying the opposite side of the tested Center and Left or Right off axis position until the 2 Point (pt) average Thermocouple Test Temperature value is within the tolerance limits. This will mitigate some heat gun variability. If the testing is not successful, replace the heat gun with one with a more uniform output.

NOTE: It is recommended this value be near or approximately at the mid-point of the temperature range defined by the tolerance in Table 1.

(k) Record the two (2) point average Thermocouple Test Temperature verification temperature under the pre-test remarks Data Sheet in Table 2 (Refer Appendix A) for reference only.

(2) For Center Wire Resistance (CWR) Measurements

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR (CFD) –

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION

January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 15 of 30

NOTE: CWR Measurements must be taken with an LCR meter and not a DMM. There a re Sensing Elem ent DC offset volta ge restrictions tha t a re required to be m a intained as well as electrical connection constraints to prevent Sensing Element polarization damage risk.

o The LCR meter shall be configured as follows:

ƒ Measurement mode: Resistance (R) ƒ Range: 100 Ω or 200 Ω as applicable

o The LCR meter shall be capable of meeting the following requirements:

ƒ Frequency: 1 kHz ƒ Bias: 0.6-1.0 Vrms, 0 Vdc offset

NOTE: These settings must be set at the meter if configurable or it must be confirmed that the meter is capable of these settings if not configurable.

(3) For Salt Core Impedance (SCI) Measurements o The LCR meter shall be configured as follows:

ƒ Measurement mode: Impedance (Z) ƒ Heated range: 10 Ω or 10000 Ω as applicable ƒ Room Tem perature Impedance range: 10000 Ω or 10MΩ as applicable o The LCR meter shall be capable of meeting the following requirements:

ƒ Frequency: 1 kHz ƒ Bias: 0.6-1.0 Vrms, 0 Vdc offset

CAUTION: When you do the test, do not use a meter that applies dc voltage. Do not use insulation resistance "megger" testers or dielectric voltage "hypot" testers. These will damage the sensing element.

NOTE: These settings must be set at the meter, if configurable or it must be confirmed that the meter is capable of these settings if not configurable.

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR(CFD)–

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 16 of 30 C. RC – Procedure - Bench Top Thermal Test

(1) Test locations

(a) Refer to Figure 4 below for test locations and test sections:

Figure 4. Test Locations for Compartment Overheat

(b) For sensing elements longer than 30 inch (76.2 cm) it shall be tested in three (3) locations. Testing shall NOT be performed within 1 inch (2.54 cm) of the connectors:

1) The 1 st location shall be from 2-14 inches (5-35 cm) from the beginning of the sensing element and as close to the end as limits allow. Each location will consist of 3 test points with a 3-4 inch (7.62 to 10.16 cm) center to center spacing between each test point. If the “Heated Impedance” Z value is below the Zeq(limit) for test point 1, test point 2, or test point 3, no additional test points within this test location are required and can be entered directly on the data sheet as the final Zeq(Calc).

If the “Heated Impedance” Z value is at or above the Zeq(limit) for all 3 test points, the Zeq(limit) will have to be calculated.

2) The 2 nd location shall be a location between 33% and 67% of the length of the sensing element AND at least 10 inches (25 cm) from the 1 st and 3rd test locations for sensing elements longer than 60 inches (152.4 cm). Each location will consist of 3 test points with a 3-4 inch (7.62 to 10.16 cm) center to center spacing between each test point. If the “Heated Impedance” Z value is below the Zeq(limit) for test point 1, test point 2, or test point 3, no additional test points within this test location are required and can be entered directly on the data sheet as the final Zeq(Calc).

If the “Heated Impedance” Z value is at or above the Zeq(limit) for all 3 test points, the Zeq(limit) will have to be calculated.

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR (CFD) –

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION

January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 17 of 30

3) The 3 rd location shall be from 2-14 inches (5-35 cm) from the opposite end of the sensing element and as close to the end as limits allow. Each location will consist of 3 test points with a 3-4 inch (7.62 to 10.16 cm) center to center spacing between each test point. If the “Heated Impedance” Z value is below the Zeq(limit) for test point 1, test point 2, or test point 3, no additional test points within this test location are required and can be entered directly on the data sheet as the final Zeq(Calc).

If the “Heated Impedance” Z value is at or above the Zeq(limit) for all 3 test points, the Zeq(limit) will have to be calculated.

(c) If the sensing element is between 14 - 30 inches (35 - 76.2 cm) long it shall be tested in two (2) locations. Testing shall NOT be performed within 1 inch (2.54 cm) of the connectors:

1) The 1 st location shall be from 2-14 inches (5-35 cm) from the beginning of the sensing element and as close to the end as limits allow. Each location will consist of 3 test points with a 3-4 inch (7.62 to 10.16 cm) center to center spacing between each test point. If the “Heated Impedance” Z value is below the Zeq(limit) for test point 1, test point 2, or test point 3, no additional test points within this test location are required and can be entered directly on the data sheet as the final Zeq(Calc).

If the “Heated Impedance” Z value is at or above the Zeq(limit) for all 3 test points, the Zeq(limit) will have to be calculated.

2) The 2 nd location shall be from 2-14 inches (5-35 cm) from the end of the sensing element and as close to the end as limits allow. Each location will consist of 3 test points with a 3-4 inch (7.62 to 10.16 cm) center to center spacing between each test point. If the “Heated Impedance” Z value is below the Zeq(limit) for test point 1, test point 2, or test point 3, no additional test points within this test location are required and can be entered directly on the data sheet as the final Zeq(Calc). If the “Heated Impedance” Z value is at or above the Zeq(limit) for all 3 test points, the Zeq(limit) will have to be calculated.

(d) Preformed and non-preformed sensing elements less than 14 inches (35 cm) shall be tested in one (1) location and at (1) test point furthermost distance from the connectors.

Testing shall NOT be performed within 1 inch (2.54 cm) of the connectors. Avoid aiming the heat gun at any grommets used to attach the sensing element if installed

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR (CFD) –

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION

January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 18 of 30

on a bracket. In some instances, the heat gun flange must be removed in order to effectively execute the testing of the preformed sensing elements. The preformed sensing elements shall be tested to the thermocouple test temperature identified in Table 1 plus 65°F (36°C).

1) The 1 st and only (middle) location shall be in the middle area farthest from the beginning and end of the sensing element that has a width of approximately 1.5 to

2.0 inches (3.81 to 5.08 cm).

(2) Test article preparations

(a) Remove the sensing element from packing material ensuring that the packing material is stored in a location where it will be shielded from the output of the heat gun.

(b) Uncoil the non-preformed sensing element to ensure access to the necessary start, middle, and end locations required for testing. Minimize bending to ensure easier recoiling and return to packaging. Ensure sensing elements are left straight and not bent for a minimum of 1 inch (2.54 cm) from rear hex nuts of the sensing element connectors.

CAUTION: Do not uncoil/straighten preformed sensing elements. They cannot be easily re-formed without a precision fixture.

(c) Mark the test locations using a permanent ink marker. Refer to Section 3.C.(1) Test Locations for instructions on test locations.

NOTE: Permanent Marker will not affect sensing element operation. It is not necessary to remove the markings after testing is complete.

(d) Select test cable (P/N 1146006-0254-00) {Pin Style} or (1148006-0254-00) {Socket Style}, or test contact pin (P/N 349457), or [test contact pin (P/N 349457) and shell & insert assembly (P/N 476232)], which best mate with the sensing element under test.

For sensing elements which are terminated with Lugs, the test lead can be clipped to the lug for the center wire connection and the sensing element sheath for the common connection.

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR (CFD) –

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION

January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 19 of 30

CAUTION: Use a connection cable or install a test pin in the socket connector to prevent damage to the sensing element connectors.

(e) Turn on the LCR meter. If the meter is configurable, set the LCR meter to a test frequency of 1 kHz, DC bias to 0 VDC, signal amplitude to approximately 0.8 ±0.2 Vrms, and measurement mode of “Z”. If t he meter is not configurable, using the meter specification sheet, ensure theses parameters are met on the LCR meter.

(f) Connect the LCR meter for the appropriate measurement type as described below:

For CWR measurements:

1) Connect the center wire of the connecting cable (P/N 1146006-0254-00) {Pin Style} or (1148006-0254-00) {Socket Style}, or test contact pin (P/N 349457), or [test contact pin (P/N 349457) and shell & insert assembly (P/N 476232)], which best mate with the sensing element under test on one end of the sensing element to one terminal on the LCR meter.

2) Connect the center wire of the connecting cable (P/N 1146006-0254-00) {Pin Style} or (1148006-0254-00) {Socket Style}, or test contact pin (P/N 349457), or [test contact pin (P/N 349457) and shell & insert assembly (P/N 476232)], which best mate with the sensing element under test on the other end of the sensing element to the other terminal on the LCR meter.

NOTE: It is expected that the connecting cable impedance is less than 0.25 Ohms. It may be necessary to subtract the connecting cable impedance if the tolerances in Section 2.E.(2) Table are not met.

For SCI measurements:

1) Connect the center wire of the connecting cable (P/N 1146006-0254-00) {Pin Style} or (1148006-0254-00) {Socket Style}, or test contact pin (P/N 349457), or [test contact pin (P/N 349457) and shell & insert assembly (P/N 476232)], which best mate with the sensing element under test to the plus or positive terminal on the LCR meter

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR (CFD) –

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION

January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 20 of 30

2) Connect the negative terminal on the LCR meter to the shield of the connecting cable (P/N 1146006-0254-00) {Pin Style} or (1148006-0254-00) {Socket Style} or the sensing element tube near one connector (away from the area or end being heated).

CAUTION: When connecting the cable to the sensing element, support the cable back shell with one hand and the sensing element end with the other, then twist the nut until tight. Do not twist the sensing element or the mating test cable if used.

NOTE: If using a test cable, ensure that when the mating cable is connected from pin and/or socket connectors, that the mating cable is held so that it does not rotate while threading and connecting to the sensing element connector. An incremental threading and engagement pushing while holding the connector is required to ensure the mating cable is not twisting and damaging the core cables or mating pin contacts or shell and insert assemblies. Same for disconnecting except in reverse.

(3) Test Set Up

(a) For CWR measurements:

1) Turn on the LCR meter.

2) Refer to the LCR meter operating manual to set the required measurement test conditions. Typical example would be to set the measurement parameter by selecting or entering on the applicable meter buttons (example “L/C/R/Z”); settin g the measurement frequency by selecting or entering on the applicable meter buttons (example “FREQ”); setting the measurement AC amplitude by selecting or entering on the applicable meter buttons (example “AC”); and setting the measurement DC bias to 0 by selecting or entering on the applicable meter buttons (example “DC”);

3) Set the LCR meter to Measurement parameter mode of “R”.

4) Set the LCR meter measurement frequency to 1 kHz if configurable. If the meter is not configurable, using the meter specification sheet, ensure these parameters are met on the LCR meter.

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR (CFD) –

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION

January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 21 of 30

5) Set the LCR meter measurement AC amplitude to approximately 0.8 +/- 0.2 Vrms and DC bias or offset to 0 Vdc. If the meter is not configurable, using the meter specification sheet, ensure the LCR meter parameters in Section 2.E.(2) Table are met.

6) Set the measurement range as applicable (1 00Ω or 200Ω) if applicable.

7) Connect the LCR meter to the sensing element start and the sensing element end.

NOTE: It is expected that the connecting cable impedance is less than 0.25 Ohms. It may be necessary to subtract the connecting cable impedance if the tolerances in Section 2.E.(2) Table are not met.

(b) For SCI measurements:

1) If the meter is configurable, set the LCR meter to a test frequency of 1 kHz, ensure or set DC bias to 0Vdc, AC signal amplitude to approximately 0.8 +/- 0.2 Vrms, and measurement mode of “Z”. If the meter is not configurable, using the meter specification sheet, ensure these parameters are met on the LCR meter.

2) Ensure the LCR meter is connected to the sensing element start/end and the sensing element ground (sensing element tube).

CAUTION: When you do the test, do not use a meter that applies dc voltage. Do not use insulation resistance "megger" testers or dielectric voltage "hypot" testers. These will damage the sensing element.

(4) Test Procedure

(a) Enter the top section information (P/N, S/N, date, temperature, Pre Test Remarks, etc.)

and record the results on the applicable Data Sheet in Table 2 (Refer Appendix A).

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR (CFD) –

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION

January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 22 of 30

Table 1: Heat Gun Temperature Settings Salt Type Letter Salt Temp Thermocouple Test Temperature* Family PN Zeq ohms A 255 °F / 124 °C 275 ( -0,+30) °F / 135 (- 0,+17) °C 1070001 148 1072001 148 04-90014 148 ALL OTHERS 127 C 310 °F / 154 °C 332 ( -0,+30) °F / 167 (- 0,+17) °C 1072001 81 ALL OTHERS 68 D 400 °F / 204 °C 427 -0,+30) °F / 219 (-0,+17) °C ALL 97 M 180 °F / 82 °C 196 -0,+30) °F / 91 (-0,+17) °C ALL 128 R 356 °F / 180 °C 381 (-0,+30) °F / 194 (-0,+17) °C ALL 81 * For preformed sensing elements 14” (35 cm) or less, the Thermocouple Test Temperature will be the value stated in Table 1 plus 65 °F (36 °C)

Note: The Salt Type is designated by the P/N in one of two ways:

The letter in the P/N (i.e. 04-90014-9238A is Salt Type “A”) The end dash number (i.e. 35535-2-310 is Salt Type “C”) P/N’s 04 -90016-901, 04-90016-902, 1094006-046, & 1095006-046 are Salt Type “R”

WARNING: If the hot air is set above 392 °F (200 °C), ensure the surroundings are free of fuel vapors and other ignition sources.

(b) Measure the Center Wire Resistance and log the value in the Data Sheet Table 2 (Refer Appendix A).

(c) Turn on the heat gun and set and verify the temperature at the interval frequency per Section 3.B. using the thermocouple temperature values specified in Table 1. Allow the heat gun to preheat for a minimum of 30 seconds (0.5 minutes) and must reach proper stable test temperature. Ensure that the exhaust of the heat gun is directed in a safe direction. Refer to individual P/N top level drawings to determine salt type .

(d) Measure and record the “Room Temperature Impedance” using the LCR meter and SCI Measurement criteria. The value must be ≥ 10 k Ω and < 3M Ω. Log the value on the Data Sheet Table 2 (Refer Appendix A). Refer to Section 3.C.(5).(b). Post Test for values that are out of tolerance.

KIDDE AEROSPACE & DEFENSE

SERVICE BULLETIN FIRE PROTECTION – AIRBUS CONTINUOUS FIRE DETECTOR (CFD) –

AIRBUS SENSING ELEMENT - FIELD TESTING OF CFD FOR PROPER

OPERATION

January 13/22 CFD-26-3 523-0832622 U.S. Export Classification: EAR 9E991 Page 23 of 30

NOTE: If the “Room Temperature Impedance” is ≥ 3M Ω check LCR meter lead continuity by shorting leads together and then verify LCR meter to sensing element lead connections and retest if necessary.

(e) Heat the 1 st test point in the first test location for a minimum of 60 seconds (1 minute) and no more than 120 seconds (2 minutes). Refer to Section 3.B.(4).(a) Test Locations for instructions on test locations.

NOTE: If the “Heated Impedance” is below the Zeq(limit) for five (5) or more seconds prior to 60 seconds, the full 60 seconds wait time is NOT required (can proceed to next test location).

NOTE: For optimum test execution it is best to measure the CWR value first, then calculate the Zeq(limit). Perform the individual heated test points and assess if they are below the Zeq(limit). If not, continue heating additional local test points up to three

(3) total before advancing to the next test location of the sensing element. Individual Z re adings are not required to be ≤ Zeq(limit). Individual Z readings must be >0.4 Ω and < 3 M Ω (the upper room temperature impedance limit). Repeat the same testing method until all three (3) test locations of the sensing element are tested. Then go back and perform the Zeq(Calc) math calculations to assess pass/fail.

(f) Measure and record the “Heated Impedance” using the LCR meter and SCI Measurement criteria. Repeat Steps e) to g) for a total of three (3) times within this test location area (3 readings) with a 3 to 4 inch (7.62 to 10.16 cm) spacing.

NOTE: If the “Heated Impedance” Z value is below the Zeq(limit) for test point 1, test point 2, or test point 3, no additional test points within this test location are required and can be entered directly on the data sheet as the final Zeq(Calc).

(g) Record each value on the Data Sheet and then use the values to calculate the Zeq(calc) value using the formula below: