(2) Typical low-level load devices have a voltage of less than 0.5 volts and a continuous current of less than 0.5 amps. A suitable method of rating switches for use on logic load devices is specified in ANSI/EIA 5200000.
h. Shock and Vibration.
(1) Electromechanical switches (toggle switches) are most susceptible to shock and vibration in the plane that is parallel to contact motion. Under these conditions the switch contacts may momentarily separate.
ANSI/EIA 5200000 specifies that contact separations greater than 10 microseconds and that closing of open contacts in excess of 1 microsecond are failures. Repeated contact separations during high levels of vibration or shock may cause excessive electrical degradation of the contacts. These separations can also cause false signals to be registered by electronic data processors without proper buffering.
(2) Although proximity switches do not have moving parts, the reliability of the inter - nal electronic parts of the switch may be reduced. Reliability and mean time betweenfailure (MTBF) calculations should reflect the applicable environment. Note that the mounting of both the proximity sensor and its target must be rigid enough to withstand shock or vibration to avoid creating false responses.
i. Electromagnetic/Radio Frequency Interference (EMI/RFI).
(1) DC operated electromechanical switches are usually not susceptible to EMI/RFI. Proximity switches are susceptible to an EMI/RFI environment and must be evaluated in the application. Twisting lead wires, metal overbraids, lead wire routing, and the design of the proximity switch can minimize susceptibility.
(2) The arcing of electromechanical switch contacts generates short duration EMI/RFI when controlling highly inductive electrical loads. Twisting lead wires, metal overbraids, and lead wire routing can reduce or eliminate generation problems when dealing with arcing loads. Proximity sensors generally use a relatively low-energy electromagnetic field to sense the target. Adequate spacing is required to prevent interference between adja - cent proximity sensors or other devices susceptible to EMI/RFI. Refer to manufacturer’s instructions.
b. Temperature.
(1) Electromechanical switches can withstand wide temperature ranges and rapid gradient shifts without damage. Most aircraft switches operate between -55 °C and 85 °C with designs available from -185 °C to 260 °C or more. Higher temperatures require more exotic materials, which can increase costs and limit life. It should be noted that o-ring seals and elastomer boot seals tend to stiffen in ex - treme cold. This can increase operating forces and reduce release forces or stop the switch from releasing.
(2) Proximity sensors are normally de - signed for environments from -55 °C to 125 °C. During temperature excursions, the operating and release points may shift from 5 percent to 10 percent. Reliability of the proximity sensor will typically be highest at room temperature. The reliability and MTBF estimates should be reduced for use under high temperatures or high thermal gradients.
c. Sealing.
NOTE: The materials used for sealing (o-rings, potting materials, etc.)
should be compatible with any aircraft fluids to which the switch may be exposed.
Page 11-18 Par 11-53
(1) Electromechanical switches range in sealing from partially sealed to hermetically sealed. Use a sealed switch when the switch will be exposed to a dirty environment during storage, assembly, or operation. Use a higher level of sealing when the switch will not have an arcing load to self-clean the contacts. Lowenergy loads tend to be more susceptible to contamination.
(2) Proximity switches for aircraft ap - plications typically have a metal face and pot - ting material surrounding any electronics and lead wire exits. The potting material should be compatible with the fluids the switch will be exposed to in the environment. The plastic sensing face of some proximity switches may be subject to absorption of water that may cause the operating point to shift should be protected.
d. Switch Installation. Hazardous errors in switch operation may be avoided by logical and consistent installation. “On-off” two-position switches should be mounted so that the “on” position is reached by an upward or forward movement of the toggle. When the switch controls movable aircraft elements, such as landing gear or flaps, the toggle should move in the same direction as the desired motion. Inadvertent operation of switches can be prevented by mounting suitable guards over the switches.
11-48. RELAYS. A relay is an electrically controlled device that opens and closes electrical contacts to effect the operation of other devices in the same or in another electrical circuit. The relay converts electrical energy into mechanical energy through various means, and through mechanical linkages, actuates electri - cal conductors (contacts) that control electrical circuits. Solid-state relays may also be used in electrical switching applications.
a. Use of Relays. Most relays are used as a switching device where a weight reduction can be achieved, or to simplify electrical controls. It should be remembered that the relay is an electrically operated switch, and therefore subject to dropout under low system voltage conditions.
b. Types of Connections. R e l a y s a r e manufactured with various connective means from mechanical to plug-in devices. Installation procedures vary by the type of connection and should be followed to ensure proper operation of the relay.
c. Repair. Relays are complicated electromechanical assemblies and most are not repairable.
d. Relay Selection.
(1) Contact ratings, as described on the relay case, describe the make, carry, and break capability for resistive currents only. Consult the appropriate specification to determine the derating factor to use for other types of current loads. (Ref. MIL-PRF-39016, MIL-PRF-5757, MIL-PRF-6016, MIL-PRF-835836.)
(2) Operating a relay at less than nominal coil voltage may compromise its perform - ance and should never be done without written manufacturer approval.
e. Relay Installation and Maintenance.
For installation and maintenance, care should be taken to ensure proper placement of hardware, especially at electrical connections. The use of properly calibrated torque wrenches and following the manufacturer’s installation procedures is strongly recommended. This is especially important with hermetically sealed relays, since the glass-to-metal seal (used for Par 11-53 Page 11-19
insulation of the electrically “live” components) is especially vulnerable to catastrophic failure as a result of overtorquing.
(1) When replacing relays in alternating current (ac) applications, it is essential to maintain proper phase sequencing. For any application involving plug-in relays, proper engagement of their retaining mechanism is vital.
(2) The proximity of certain magnetically permanent, magnet assisted, coil operated relays may cause them to have an impact on each other. Any manufacturer’s recommendations or precautions must be closely followed.
11-49. LOAD CONSIDERATIONS.
When switches or relays are to be used in ap - plications where current or voltage is substantially lower than rated conditions, additional intermediate testing should be performed to ensure reliable operation. Contact the manufacturer on applications different from the rated conditions.
11-50. OPERATING CONDITIONS FOR SWITCHES AND RELAYS. Switches and relays should be compared to their specification rating to ensure that all contacts are made properly under all conditions of operation, including vibration equivalent to that in the area of the aircraft in which the switch or relay is to be installed.
11-57. 11-65. [RESERVED.] Page 11-20 Par 11-54
SECTION 5. ELECTRICAL WIRE RATING
11-66. GENERAL. Wires must be sized so that they: have sufficient mechanical strength to allow for service conditions; do not exceed allowable voltage drop levels; are protected by system circuit protection devices; and meet circuit current carrying requirements.
a. Mechanical Strength of Wires. If it is desirable to use wire sizes smaller than #20, particular attention should be given to the me chanical strength and installation handling of these wires, e.g., vibration, flexing, and termi nation. Wire containing less than 19 strands must not be used. Consideration should be given to the use of high-strength alloy con ductors in small gauge wires to increase me chanical strength. As a general practice, wires smaller than size #20 should be provided with additional clamps and be grouped with at least three other wires. They should also have ad ditional support at terminations, such as con nector grommets, strain relief clamps, shrink able sleeving, or telescoping bushings. They should not be used in applications where they will be subjected to excessive vibration, re peated bending, or frequent disconnection from screw termination.
b. Voltage Drop in Wires. The voltage drop in the main power wires from the genera tion source or the battery to the bus should not exceed 2 percent of the regulated voltage when the generator is carrying rated current or the battery is being discharged at the 5-minute rate. The tabulation shown in table 11-6 de fines the maximum acceptable voltage drop in the load circuits between the bus and the utili zation equipment ground.
c. Resistance. The resistance of the cur rent return path through the aircraft structure is generally considered negligible. However, this is based on the assumption that adequate TABLE 11-6. Tabulation chart (allowable voltage drop between bus and utilization equipment ground).
Nominal Allowable voltage Intermittent system drop continuous operation voltage operation 14 0.5 1 28 1 2 115 4 8 200 7 14 bonding to the structure or a special electric current return path has been provided that is capable of carrying the required electric cur rent with a negligible voltage drop. To deter mine circuit resistance check the voltage drop across the circuit. If the voltage drop does not exceed the limit established by the aircraft or product manufacturer, the resistance value for the circuit may be considered satisfactory.
When checking a circuit, the input voltage should be maintained at a constant value. Ta bles 11-7 and 11-8 show formulas that may be used to determine electrical resistance in wires and some typical examples.
d. Resistance Calculation Methods.
Figures 11-2 and 11-3 provide a convenient means of calculating maximum wire length for the given circuit current.
(1) Values in tables 11-7 and 11-8 are for tin-plated copper conductor wires. Be cause the resistance of tin-plated wire is slightly higher than that of nickel or silverplated wire, maximum run lengths determined from these charts will be slightly less than the allowable limits for nickel or silver-plated copper wire and are therefore safe to use. Fig ures 11-2 and 11-3 can be used to derive slightly longer maximum run lengths for silver or nickel-plated wires by multiplying the maximum run length by the ratio of resistance of tin-plated wire, divided by the resistance of silver or nickel-plated wire.
Par 11-66 Page 11-21
TABLE 11-7. Examples of determining required tinplated copper wire size and checking voltage drop using figure 11-2 Voltage drop Run Lengths (Feet) Circuit Current (Amps) Wire Size From Chart Checkcalculated voltage drop (VD)= (Resistance/Ft) (Length) (Current) 1 107 20 No. 6 VD= (.00044 ohms/ft)
(107)(20)=
0.942
0.5 90 20 No. 4 VD= (.00028 ohms/ft)
(90)(20)=
0.504 4 88 20 No. 12 VD= (.00202 ohms/ft)
(88)(20)=
3.60 7 100 20 No. 14 VD= (.00306 ohms/ft)
(100)(20)=
6.12 TABLE 11-8. Examples of determining maximum tinplated copper wire length and checking voltage drop using figure 11-2.
Maximum Voltage drop Wire Size Circuit Current (Amps) Maximum Wire Run Length (Feet) Check-calculated voltage drop (VD)= (Resistance/Ft) (Length) (Current) 1 No. 10 20 39 VD= (.00126 ohms/ft)
(39)(20)= .98
0.5 --- 19.5 VD= (.00126 ohms/ft)
(19.5)(20)= .366 4 --- 156 VD= (.00126 ohms/ft)
(156)(20)=
3.93 7 --- 273 VD= (.00126 ohms/ft)
(273)(20)=
6.88
(2) As an alternative method or a means of checking results from figure 11-2, continu ous flow resistance for a given wire size can be read from table 11-9 and multiplied by the wire run length and the circuit current. For inter mittent flow, use figure 11-3.
(3) V oltage drop calculations for alumi num wires can be accomplished by multiplying the resistance for a given wire size, defined in table 11-10, by the wire run length and circuit current.
(4) When the estimated or measured conductor temperature (T2) exceeds 20 °C, such as in areas having elevated ambient tem peratures or in fully loaded power-feed wires, the maximum allowable run length (L2), must be shortened from L1 (the 20 °C value) using the following formula for copper conductor wire:
(254.5 °C)(L1)L2 = (234.5 °C)+)(T 2) For aluminum conductor wire, the formula is:
(258.1 °C)(L1)L2 = (238.1 °C) + (T 2) These formulas use the reciprocal of each ma terial’s resistively temperature coefficient to take into account increased conductor resis tance resulting from operation at elevated tem peratures.
(5) To determine T2 for wires carrying a high percentage of their current carrying capa bility at elevated temperatures, laboratory testing using a load bank and a hightemperature chamber is recommended. Such tests should be run at anticipated worse case ambient temperature and maximum currentloading combinations.
(6) Approximate T2 can be estimated using the following formula:
T2 = T1 + (TR − T1 ) ( I / I )2 max Page 11-22 Par 11-66
Where:
T1 = Ambient Temperature T2 = Estimated Conductor Temperature TR = Conductor Temperature Rating I2 = Circuit Current (A=Amps) Imax = Maximum Allowable Current (A=Amps) at TR This formula is quite conservative and will typi cally yield somewhat higher estimated tempera tures than are likely to be encountered under actual operating conditions.
Note: Aluminum wire-From Table 11-9 and 11-10 note that the conductor resistance of aluminum wire and that of copper wire (two numbers higher) are similar. Accordingly, the electric wire current in Table 11-9 can be used when it is desired to substitute aluminum wire and the proper size can be se - lected by reducing the copper wire size by two numbers and referring to Table 11-10.
The use of aluminum wire size smaller than No. 8 is not recommended.
TABLE 11-9. Current carrying capacity and resistance of copper wire.
Wire Size Continuous duty current (amps)-Wires in bundles, groups, harnesses, or conduits. (See Note #1) Max. resistance ohms/1000ft@20 °C tin plated conduc tor (See Note #2) Nominal conductor area circ.mils Wire Conductor Temperature Rating 105 °C 150 °C 200 °C 24 2.5 4 5 28.40 475 22 3 5 6 16.20 755 20 4 7 9 9.88 1,216 18 6 9 12 6.23 1,900 16 7 11 14 4.81 2,426 14 10 14 18 3.06 3,831 12 13 19 25 2.02 5,874 10 17 26 32 1.26 9,354 8 38 57 71 0.70 16,983 6 50 76 97 0.44 26,818 4 68 103 133 0.28 42,615 2 95 141 179 0.18 66,500 1 113 166 210 0.15 81,700 0 128 192 243 0.12 104,500 00 147 222 285 0.09 133,000 000 172 262 335 0.07 166,500 0000 204 310 395 0.06 210,900 Note #1: Rating is for 70°C ambient, 33 or more wires in the bundle for sizes 24 through 10, and 9 wires for size 8 and larger, with no more than 20 percent of harness current carrying capacity being used, at an operating altitude of 60,000 feet. For rating of wires under other conditions or configurations see paragraph 11-69.
Note #2: For resistance of silver or nickel-plated conductors see wire specifications.
Par 11-66 Page 11-23
TABLE 11-10. Current carrying capacity and resistance of aluminum wire.
Wire Size Continuous duty current (amps) Wires in bundles, groups or harnesses or conduits (See table 11-9 Note #1) Max. resistance ohms/1000ft Wire conductor temperature rating @ 20 °C 105 °C 150 °C 8 6 4 2 1 0 00 000 0000 30 40 54 76 90 102 117 138 163 45 61 82 113 133 153 178 209 248
1.093
0.641
0.427
0.268
0.214
0.169
0.133
0.109
0.085 Note: Observe design practices described in paragraph 11-67 for aluminum conductor Page 11-24 Par 11-66
11-67. METHODS FOR DETERMINING
CURRENT CARRYING CAPACITY OF WIRES. This paragraph contains methods for determining the current carrying capacity of electrical wire, both as a single wire in free air and when bundled into a harness. It presents derating factors for altitude correction and ex amples showing how to use the graphical and tabular data provided for this purpose. In some instances, the wire may be capable of carrying more current than is recommended for the contacts of the related connector. In this instance, it is the contact rating that dictates the maximum current to be carried by a wire.
Wires of larger gauge may need to be used to fit within the crimp range of connector con tacts that are adequately rated for the current being carried. Figure 11-5 gives a family of curves whereby the bundle derating factor may be obtained.
a. Effects of Heat Aging on Wire Insulation. Since electrical wire may be installed in areas where inspection is infrequent over ex tended periods of time, it is necessary to give special consideration to heat-aging character istics in the selection of wire. Resistance to heat is of primary importance in the selection of wire for aircraft use, as it is the basic factor in wire rating. Where wire may be required to operate at higher temperatures due either to high ambient temperatures, high-current load ing, or a combination of the two, selection should be made on the basis of satisfactory performance under the most severe operating conditions.
b. Maximum Operating Temperature.
The current that causes a temperature steady state condition equal to the rated temperature of the wire should not be exceeded. Rated temperature of the wire may be based upon the ability of either the conductor or the insulation to withstand continuous operation without deg radation.
c. Single Wire in Free Air. Determining a wiring system’s current carrying capacity be gins with determining the maximum current that a given-sized wire can carry without ex ceeding the allowable temperature difference (wire rating minus ambient °C). The curves are based upon a single copper wire in free air.
(See figures 11-4a and 11-4b.)
d. Wires in a Harness. When wires are bundled into harnesses, the current derived for a single wire must be reduced as shown in fig ure 11-5. The amount of current derating is a function of the number of wires in the bundle and the percentage of the total wire bundle ca pacity that is being used.
e. Harness at Altitude. Since heat loss from the bundle is reduced with increased al titude, the amount of current should be de rated. Figure 11-6 gives a curve whereby the altitude-derating factor may be obtained.
f. Aluminum Conductor Wire. W h e n aluminum conductor wire is used, sizes should be selected on the basis of current ratings shown in table 11-10. The use of sizes smaller than #8 is discouraged (Ref. AS50881A).
Aluminum wire should not be attached to en gine mounted accessories or used in areas having corrosive fumes, severe vibration, me chanical stresses, or where there is a need for frequent disconnection. Use of aluminum wire is also discouraged for runs of less than 3 feet (AS50991A). Termination hardware should be of the type specifically designed for use with aluminum conductor wiring.
11-68. INSTRUCTIONS FOR USE OF ELECTRICAL WIRE CHART.
a. Correct Size. To select the correct size of electrical wire, two major requirements must be met:
Par 11-67 Page 11-25
(1) The wire size should be sufficient to prevent an excessive voltage drop while car rying the required current over the required distance. (See table 11-6, Tabulation Chart, for allowable voltage drops.)
(2) The size should be sufficient to pre vent overheating of the wire carrying the re quired current. (See paragraph 11-69 for al lowable current carrying calculation methods.)
b. Two Requirements. To meet the two requirements (see paragraph 11-66b) in se lecting the correct wire size using figure 11-2 or figure 11-3, the following must be known:
(1) The wire length in feet.
(2) The number of amperes of current to be carried.
(3) The allowable voltage drop permitted.
(4) The required continuous or inter mittent current.
(5) The estimated or measured con ductor temperature.
(6) Is the wire to be installed in conduit and/or bundle?
(7) Is the wire to be installed as a single wire in free air?
c. Example No. 1. Find the wire size in figure 11-2 using the following known infor mation:
(1) The wire run is 50 feet long, in cluding the ground wire.
(2) Current load is 20 amps.
(3) The voltage source is 28 volts from bus to equipment.
(4) The circuit has continuous opera tion.
(5) Estimated conductor temperature is 20 °C or less.
The scale on the left of the chart represents maximum wire length in feet to prevent an ex cessive voltage drop for a specified voltage source system (e.g., 14V , 28V , 115V , 200V).
This voltage is identified at the top of scale and the corresponding voltage drop limit for continuous operation at the bottom. The scale (slant lines) on top of the chart represents am peres. The scale at the bottom of the chart rep resents wire gauge.
STEP 1: From the left scale find the wire length, 50 feet under the 28V source column.
STEP 2: Follow the corresponding horizontal line to the right until it intersects the slanted line for the 20-amp load.
STEP 3: At this point, drop vertically to the bottom of the chart. The value falls between No. 8 and No. 10. Select the next larger size wire to the right, in this case No. 8. This is the smallest size wire that can be used without ex ceeding the voltage drop limit expressed at the bottom of the left scale. This example is plot ted on the wire chart, figure 11-2. Use figure 11-2 for continuous flow and figure 11-3 for intermittent flow.
d. Procedures in Example No. 1 para graph 11-68c, can be used to find the wire size for any continuous or intermittent operation (maximum two minutes). V oltage (e.g.
14 volts, 28 volts, 115 volts, 200 volts) as in dicated on the left scale of the wire chart in figure 11-2 and 11-3.
e. Example No. 2. Using figure 11-2, find the wire size required to meet the allowable voltage drop in table 11-6 for a wire carrying Page 11-26 Par 11-68
current at an elevated conductor temperature using the following information:
(1) The wire run is 15.5 feet long, in cluding the ground wire.
(2) Circuit current (I2) is 20 amps, continuous.
(3) The voltage source is 28 volts.
(4) The wire type used has a 200 °C conductor rating and it is intended to use this thermal rating to minimize the wire gauge.
Assume that the method described in para graph 11-66d(6) was used and the minimum wire size to carry the required current is #14.
(5) Ambient temperature is 50 °C under hottest operating conditions.
f. Procedures in example No. 2.
STEP 1: Assuming that the recommended load bank testing described in para graph 11-66d(5) is unable to be conducted, then the estimated calculation methods out lined in paragraph 11-66d(6) may be used to determine the estimated maximum current (Imax). The #14 gauge wire mentioned above can carry the required current at 50 °C ambient (allowing for altitude and bundle derating).
(1) Use figure 11-4a to calculate the Imax a #14 gauge wire can carry.
Where:
T2 = estimated conductor temperature T1 = 50 °C ambient temperature TR = 200 °C maximum conductor rated temperature
(2) Find the temperature differences (TR-T1) = (200 °C-50 °C) = 150 °C.
(3) Follow the 150 °C corresponding horizontal line to intersect with #14 wire size, drop vertically and read 47 Amps at bottom of chart (current amperes).
(4) Use figure 11-5, left side of chart reads 0.91 for 20,000 feet, multiple
0.91 x 47 Amps = 42.77 Amps.
(5) Use figure 11-6, find the derate factor for 8 wires in a bundle at 60 percent.
First find the number of wires in the bundle (8) at bottom of graph and intersect with the 60 percent curve meet. Read derating factor, (left side of graph) which is 0.6. Multiply
0.6 x 42.77 Amps = 26 Amps.
Imax = 26 amps (this is the maximum current the #14 gauge wire could carry at 50°C ambient L1=15.5 feet maximum run length for size #14 wire carrying 20 amps from figure 11-2 STEP 2: From paragraph 11-66d (5) and (6), determine the T 2 and the resultant maximum wire length when the increased resistance of the higher temperature conductor is taken into account.
T2 = T1 + (TR − T1 )( I / I )2 max T2 = 50 °C + (200 C − 50 C)( 20A / 26A = 50 °C+(150 °C)(.877) T2 = 182 °C
(254.5 °C)(L1)L2 = = (234.5 °C) + (T2)
(254.5 °C)(15.5Ft)L2 = (234.5 °C) + (182 °C)
L2 = 9.5 ft
Par 11-67 Page 11-27
The size #14 wire selected using the methods outlined in paragraph 11-66d is too small to meet the voltage drop limits from figure 11-2 for a 15.5 feet long wire run.
STEP 3: Select the next larger wire (size #12) and repeat the calculations as follows:
L1=24 feet maximum run length for 12 gauge wire carrying 20 amps from fig ure 11-2.
Imax = 37 amps (this is the maximum current the size #12 wire can carry at 50 °C ambient.
Use calculation methods outlined in para graph 11-69 and figure 11-4a.
o o oT2 = 50 C + (200 C - 50 C) ( 20A / 37A = o o o50 C + (150 C)(-540) = 131 C
254.5 o C(L1 )L = 2
234.5 o C + (T2 )
(254.5 o C)(24ft) 6108L = = 2 o o(234.5 C) + (131 C) 366
(254.5 o C)(24ft)L2 = = 16.7 ft 366 The resultant maximum wire length, after ad justing downward for the added resistance as sociated with running the wire at a higher tem perature, is 15.4 feet, which will meet the original 15.5 foot wire run length requirement without exceeding the voltage drop limit ex pressed in figure 11-2.
11-69. COMPUTING CURRENT CARRY - ING CAPACITY.
a. Example 1. Assume a harness (open or braided), consisting of 10 wires, size #20, 200 °C rated copper and 25 wires, size #22, 200 °C rated copper, will be installed in an area where the ambient temperature is 60 °C and the vehicle is capable of operating at a 60,000-foot altitude. Circuit analysis reveals that 7 of the 35 wires in the bundle (7/35 = 20 percent) will be carrying power cur rents nearly at or up to capacity.
STEP 1: Refer to the “single wire in free air” curves in figure 11-4a. Determine the change of temperature of the wire to determine free air ratings. Since the wire will be in an ambient of 60 ºC and rated at 200 ° C, the change of to temperature is 200 °C - 60 °C = 140 °C. Fol low the 140 °C temperature difference hori zontally until it intersects with wire size line on figure 11-4a. The free air rating for size #20 is 21.5 amps, and the free air rating for size #22 is 16.2 amps.
STEP 2: Refer to the “bundle derating curves” in figure 11-5, the 20 percent curve is selected since circuit analysis indicate that 20 percent or less of the wire in the harness would be car rying power currents and less than 20 percent of the bundle capacity would be used. Find 35 (on the abscissa) since there are 35 wires in the bundle and determine a derating factor of
0.52 (on the ordinate) from the 20 percent curve.
STEP 3: Derate the size #22 free air rating by multiplying 16.2 by 0.52 to get 8.4 amps inharness rating. Derate the size #20 free airrating by multiplying 21.5 by 0.52 to get
11.2 amps in-harness rating.
STEP 4: Refer to the “altitude derating curve” of figure 11-6, look for 60,000 feet (on the ab scissa) since that is the altitude at which the vehicle will be operating. Note that the wire must be derated by a factor of 0.79 (found on the ordinate). Derate the size #22 harness rating by multiplying
8.4 amps by 0.79 to get 6.6 amps. Derate the size #20 harness rating by multiplying
11.2 amps by 0.79 to get 8.8 amps.
STEP 5: To find the total harness capacity, multiply the total number of size #22 wires by the derated capacity (25 x 6.6 = 165.0 amps) and add to that the number of size #20 wires Page 11-28 Par 11-68
multiplied by the derated capacity (10 x 8.8 = 88 amps) and multiply the sum by the 20 percent harness capacity factor. Thus, the total harness capacity is
(165.0 + 88.0) x 0.20 = 50.6 amps. It has been determined that the total harness current should not exceed 50.6 A, size #22 wire should not carry more than 6.6 amps and size #20 wire should not carry more than 8.8 amps.
STEP 6: Determine the actual circuit current for each wire in the bundle and for the whole bundle. If the values calculated in step #5 are exceeded, select the next larger size wire and repeat the calculations.
b. Example 2. Assume a harness (open or braided), consisting of 12, size #12, 200 °C rated copper wires, will be operated in an am bient of 25 °C at sea level and 60 °C at a 20,000-foot altitude. All 12 wires will be op erated at or near their maximum capacity.
STEP 1: Refer to the “single wire in free air” curve in figure 11-4a, determine the tempera ture difference of the wire to determine free air ratings. Since the wire will be in ambient of 25 °C and 60 °C and is rated at 200 °C, the temperature differences are 200 °C-25 °C = 175 °C and 200 °C-60 °C = 140 °C respec tively. Follow the 175 °C and the 140 °C tem perature difference lines on figure 11-4a until each intersects wire size line, the free air rat ings of size #12 are 68 amps and 61 amps, re spectively.
STEP 2: Refer to the “bundling derating curves” in figure 11-5, the 100 percent curve is selected because we know all 12 wires will be carrying full load. Find 12 (on the abscissa) since there are 12 wires in the bundle and de termine a derating factor of 0.43 (on the ordi nate) from the 100 percent curve.
STEP 3: Derate the size #12 free air ratings by multiplying 68 amps and 61 amps by 0.43 to get 29.2 amps and 26.2 amps, respectively.
STEP 4: Refer to the “altitude derating curve” of figure 11-6, look for sea level and 20,000 feet (on the abscissa) since these are the conditions at which the load will be car ried. The wire must be derated by a factor of
1.0 and 0.91, respectively.
STEP 5: Derate the size #12 in a bundle rat ings by multiplying 29.2 amps at sea level and
26.6 amps at 20,000 feet by 1.0 and 0.91, re spectively, to obtained 29.2 amps and
23.8 amps. The total bundle capacity at sea level and 25 °C ambient is
29.2x12=350.4 amps. At 20,000 feet and 60 °C ambient the bundle capacity is
23.8x12=285.6 amps. Each size #12 wire can carry 29.2 amps at sea level, 25 °C ambient or
23.8 amps at 20,000 feet, and 60 °C ambient.
STEP 6: Determine the actual circuit current for each wire in the bundle and for the bundle.
If the values calculated in Step #5 are ex ceeded, select the next larger size wire and re peat the calculations.
Par 11-67 Page 11-29